Super Systems 20PQ User Manual

Page 47

Advertising
background image

43

CnF. 3

- Main control output conditioning - [C.F06]

This parameter will be available only when main control output is
configured.
Range: norñ

= The control output is calculated by the PID.

CñPL = The control output is complemented (100-PID

calculated value).

Ouic

= The control output is conditioned to match a

“QUICK OPENING” flow characteristic.

Eou

= The control output is conditioned to match an

“EQUAL PERCENTAGE” flow characteristic.

NOTE about output conditioning
Sometimes non linear valves are used where a linear valve is
suitable.
In these cases, it is advisable to linearize the ratio between flow
rate and valve travel in order to obtain a better control of the
process.
This instrument allows you to select an output linearization in
accordance with the two most common valve flow characteris-
tics:
- Quick opening
- Equal percentage.