Super Systems 20PQ User Manual

Page 150

Advertising
background image

146

Output limiters.
For the main and/or secondary control outputs it is possible to
set:
- output high limits
- output low limits
- output max. rate of rise.
AUTO/MANUAL mode: selectable by front push-button or logic
input.

OUTPUTS

Control output updating time :
- 125 ms when a linear input is selected
- 250 ms when a TC or RTD input is selected.
Action: direct/reverse programmable
Output level limiter:
- high and low limits for main control output
- high and low limits for secondary control output.

Out 1 and 2
Function
: singularly programmable as
- Control output
- Alarm output
- Event output.
Type: Relay, SSR or TRIAC.

Out 1 and 2 - Relay
Relay type
: SPDT
Contact rating: 3 A @ 250 V on resistive load.