33

CnF. 1

Real curve

Read-out

Adjusted
curve

Input

OFSt

2) Changing the value of this parameter, the "brG.L" (bargraph -

initial scale value [C.I03]) and "rL" (set point low limit [r.E12])
parameters will be realigned to it.
If a linear input is selected, also the “SS.th” (threshold for soft
start [C.I09]) will be realigned to it.

- Read-out- full scale value - [C.d06]

Ranges: - from -1999 to 9999 for linear input (Input range 31 to

38),

- from 0 to 9999 for linear input with square root

extraction,

- from "ñ.In.L" (read-out- initial scale value [C.d05]) to

full range value for TC/RTD input.

NOTES:
1) Changing the value of this parameter, the "brG.H" (bargraph -

full scale value [C.I04]) and "rH" (set point high limit [r.E13])
parameters will be realigned to it.

2) The programmed input span, in absolute value, must be

greater than:
300 °C or 550 °F for TC inputs
100°C or 200 °F for RTD inputs
100 digits for linear inputs.

- Offset on the main input - [C.d07]

Ranges: from -500 to 500.
NOTE: the decimal point will be automatically positioned as
selected for the main input.

- Filter on the displayed value - [C.d08]

Ranges: from 0 (no filter) to 8 seconds.
NOTE: this is a first order digital filter applied to the read-out of
the main input.