Super Systems 20PQ User Manual

Page 45

Advertising
background image

41

CnF. 3

resulting real outputs are shown below:

where:
- for the first split output (MAIN)

Bias 1 = -A
Gain 1 = 100 / (B - A)

- For the second split output (SECONDARY)

Bias 2 = -C
Gain 2 = 100 / (D - C)

FOR EXAMPLE:
Let's suppose that the first split output operates from 0 % to
33.3 % of the calculated output while the second one operates
from 33.3 % to the 100 % of the calculated output.

Where: A = 0 %

B = C = 33.3 %
D = 100 %

A

B

C

D

0 %

100 %

100 %

Calculated
PWR Output

Real PWR
Output

First split
output (MAIN)

Standard curve

Second split
output
(Secondary)

33.3 %

0 %

100 %

100 %

Calculated
PWR Output

Real PWR
Output

First split
output (MAIN)

Standard curve

Second split
output
(Secondary)

A

B e C

D

XKP-1-C2.p65

10/30/01, 9:37 AM

41