Super Systems 20PQ User Manual

Page 120

Advertising
background image

116

Gr. P

- Program 1 - Segment 1 - segment duration
- [r.A07]

This parameter can be modified only when the selected program is
not running, it is not a linked program and "t.rñP" parameter (ramp
engineering units [rA.03]) is different from "GrAd".
Upper display: xx.yy

where
xx is the number of the selected program
yy is the number of the selected segment

Lower display: "hh.ññ" for hours and minutes

"ññ.ss" for minutes and seconds.

Range: from 00.01 to 99.59

- Program 1 - Segment 1 - Gradient - [r.A08]

This parameter can be modified only when the selected program
is not running, it is not a linked program and "t.rñP" parameter
(ramp engineering units [rA.03]) is equal to "GrAd".
Upper display: xx.yy

where
xx is the number of the selected program
yy is the number of the selected segment

Range: from 1 to 9999 digit/hour

- Program 1 - Segment 1 - PID group selection
- [r.A09]

This parameter can be modified only when the selected program
is not running, it is not a linked program and at least one control
output is programmed.
Upper display: xx.yy

where
xx is the number of the selected program
yy is the number of the selected segment

Lower display: P.i.d.G
Range: from 0 to 5

NOTE: setting "Pid.G" equal to 0, the instrument will
maintain, for this segment, the PID value selected for the
previous segment or mode.

- Program 1 - Segment 1 - tracking group
selection - [r.A10]

This parameter can be modified only when the selected program
is not running, it is not a linked program and at least one control
output is programmed.
Upper display: xx.yy

where
xx is the number of the selected program
yy is the number of the selected segment

XKP-1-C2.p65

10/30/01, 9:37 AM

116

Advertising