Super Systems 20PQ User Manual

Page 90

Advertising
background image

86

Gr. 6

Run time group 6 [r.Fxx]
ALARM SETTING

- Alarm 1 type - [r.F01]

This parameter is available only when OUT 1 is configured as
alarm 1 output (“O1.Fn” [C.E01] = “ALr.1”)
Range: Proc = Alarm on process variable

bAnd = Band alarm on process variable
dEV

= Deviation alarm on process variable

ñAin = Alarm on Main control output value
SECn = Alarm on Secondary control output value

NOTE: When alarm type has been changed the alarm threshold
will be forced to its default value and alarm status will be
deleted.

- Alarm 1 configuration - [r.F02]

This parameter is available only when OUT 1 is configured as
alarm 1 output (“O1.Fn” [C.E01] = “ALr.1”)
Range: H.A.

= High alarm (outside band) with automatic reset

L.A.

= Low alarm (inside band) with automatic reset

H.A.Ac= High alarm (outside band) with automatic reset

and acknowledge

L.A.Ac= Low alarm (inside band) with automatic reset

and acknowledge

H.L.

= High alarm (outside band) with manual reset

L.L.

= Low alarm (inside band) with manual reset

NOTE: When alarm configuration has been changed, the alarm
status will be deleted.

XKP-1-C2.p65

10/30/01, 9:37 AM

86

Advertising