SMART FUNCTION

It is used to automatically optimize the control action.
To enable the SMART function proceed as follows:
1) push the MENU push-button until "Gr. 2" run time parameter

group is shown.

2) push the FUNC push-button until "Sñrt" parameter is shown.
3) push

s or t and set the "On" indication on the middle

display;

4) push the FUNC push-button.
The ST LED is flashing during the first part of SMART algorithm
(TUNE) while it is stready lit during the second one (ADAP-
TIVE).
When the smart function is enabled, it is possible to display but not
to modify the control parameters.
To disable the SMART function proceed as follows:
1) push the MENU push-button until "Gr. 2" run time parameter

group is shown.

2) push the FUNC push-button until "Sñrt" parameter is shown.
3) push

s or t and set the "OFF" indication on the middle

display;

4) push the FUNC push-button.
The ST LED will turn off.
The instrument maintains the current set of control parameters
and it enables parameter modification.

NOTES:

1) When ON/OFF control is programmed (Pb=0), the

SMART function is disabled.

2) The SMART enabling/disabling can be protected

by safety key.