Temperature drift: (CJ excluded)
< 200 ppm/°C of span for mV and TC ranges 3, 4, 7, 18, 19, 22.
< 300 ppm/°C of span for mA/V
< 250 ppm/°C of span for TC range 1, 2, 5, 6, 8, 9, 10, 14, 16,

17, 20, 21, 23, 24, 25, 29.

< 350 ppm/°C of span TC ranges 11, 12, 13, 26, 27, 28.
< 500 ppm/°C of span for RTD.
Operative temperature: from 0 to 50 °C (+32 to 122 °F).
Storage temperature: -20 to +70 °C (-4 to 158 °F)
Humidity: from 20 % to 85% RH, non condensing.

INPUTS

A) THERMOCOUPLE
Type:
J, K, T, E, N, S, R, B, L, U, G, D, C, Ni/Ni 18% Mo. °C/°F
selectable.
External resistance: 100

W max, maximum error 0,1% of span.

Cold junction: automatic compensation from 0 to 50 °C.
Cold junction accuracy : 0.1 °C/°C
Input impedance: > 1 M

W

Calibration : according to IEC 584-1 and DIN 43710 - 1977.

T/C

type

L
J

K

T

U
E
N
S
R
B
G
D
C

Ni

L
J

K

T

U
E

Ranges

1
2
3
4
5
6
7
8
9

10
11
12
13
14
16
17
18
19
20
21

-100 / 900

°C

-100 / 1000

°C

-100 / 1370

°C

-200 / 400

°C

-200 / 600

°C

-100 / 800

°C

-100 / 1400

°C

- 50 / 1760

°C

- 50 / 1760

°C

0 / 1820

°C

0 / 2300

°C

0 / 2300

°C

0 / 2300

°C

0 / 1100

°C

-150 / 1650 °F
-150 / 1830 °F
-150 / 2500 °F
-330 / 750 °F
-330 / 1110 °F
-150 / 1470 °F

DIN 43710-1977
IEC 584-1
IEC 584-1
IEC 584-1
DIN 43710-1977
IEC 584-1
IEC 584-1
IEC 584-1
IEC 584-1
IEC 584-1

DIN 43710-1977
IEC 584-1
IEC 584-1
IEC 584-1
DIN 43710-1977
IEC 584-1