Super Systems 20PQ User Manual

Page 38

Advertising
background image

34

CnF. 1

- Auxiliary input function - [C.d09]

Range: nonE = Input not used

bIAS = Input used as bias for local set point

NOTES:
1) When auxiliary input option is not mounted the middle display

will show “no.Pr” (not present).

2) When "bIAS" is selected, the instrument adds to the local set

point the value measured by the auxiliary input and scaled by
"A.In.L" [C.d11] and "A.In.H" [C.d12] parameters.

- Auxiliary input type - [C.d10]

This parameter will be skipped when the auxiliary input option is
not mounted or "A.In.F" (auxiliary input function [C.d09]) is equal
to "nonE".
Range: 0-20

= 0

-20 mA

4-20

= 4

-20 mA

0- 5

= 0

- 5 V

1- 5

= 1

- 5 V

0-10

= 0

-10 V

2-10

= 2

-10 V

- Initial scale read-out of the auxiliary input
- [C.d11]

This parameter is available only when auxiliary input is
configured
Range: from -1999 to 9999
NOTE: the decimal point will be automatically positioned as
selected for the main input.

- Full scale read-out of the auxiliary input
- [C.d12]

This parameter is available only when auxiliary input is
configured.
Range: from -1999 to 9999
NOTE: the decimal point will be automatically positioned as
selected for the main input.