II) Exiting from the configuration group 2 also the following

actions are automatically performed:
A) The "Añ.UL” parameter ("Output value for auto to manual

transfer" [C.G04]) will be forced to "bumpless" (“buñ”) if:
1) its value is < 0 and only one control output is configured;
2) servomotor open loop is configured.

B) The “SF.Cn” parameter ("Condition for output safety value"

[C.G09]) will be forced to "standard" (“Std.”) if it is not
complied with configured control output type.

C) The “SF.UL” parameter ("Output safety value" [C.G10]) will

be forced to 0 if only one control output is configured and its
value is < 0.

D) The “Fd.Fn” parameter ("Out failure detection current

measurement" [C.I11]) will be forced to “nonE” if it is
assigned to a control output different from a time
proportional output.

E) The “Fd.Ou” parameter ("Out failure detection output

assignment" [C.I13]) will be forced to “nonE” if it is
assigned to an output configured as control output.

F) The “IP” parameter ("Integral pre-load" [r.d05]) will be forced

to 50.0 if only one control output is configured and its value is
< 0.

CONFIGURATION GROUP 3 [C.Fxx]
CONTROL OUTPUT CONFIGURATION

- Split range - [C.F01]

This parameter will be available only when two control outputs
are configured.
Range: dIS

= Split range feature is not required

Enb

= Split range feature is required

NOTE about the split range.
This function allows you to drive by the same control action, two
physical outputs (two actuators) with different bias and gain.
The relation between the Calculated Power Output and the