Super Systems 20PQ User Manual

Page 43

Advertising
background image

39

CnF. 2

- OUT 6 retransmission full scale value
- [C.E15]

This parameter will be available only when Out 6 function
[C.E12] is configured as “PV.rt” or “SP.rt”
Range: From -1999 to 9999
NOTE: Decimal point is positioned as previously selected at

“CnF.1 - ñ.In.d” [C.d03])

- OUT 6 filter on the retransmitted value
- [C.E16]

This parameter will be available only when OUT 6 is configured
as process variable retransmission ("O6.Fn" [C.E12] is equal to
“PV.rt”).
Range: From 0 (no filter) to 8 seconds
NOTE: this is a first order digital filter applied to the
retransmitted output value.

General note about configuration group 2
I) Exiting from the configuration group 2 the instrument

automatically verifies the congruence of all parameters.
If a wrong setting is detected, the device will show:

Pushing the FUNC pushbutton, verify (and modify if
necessary) all group 2 parameter settings in order to assure
that the following conditions are respected:
a) Only one of the 6 outputs is configured as main output

(“ñAin”)

b) Only one of the 6 outputs is configured as secondary

output (“SECn”)

c) If only one control output is configured, it should be the

main control output (“ñAin”)

d) The servomotor must be “close loop” type if it is one of two

control outputs.

NOTE: The instrument may be used as an indicator, so that this
test is satisfied even if no output is configured as control output

XKP-1-C2.p65

10/30/01, 9:37 AM

39