Super Systems 20PQ User Manual

Page 151

Advertising
background image

147

Out 1 and 2 - SSR
Type: not
isolated voltage output
- Logic level 1:

14V @ 20 mA max.
24 V @ 1 mA.

- Logic level 0:

< 0.5 V D.C.

Out 1 and 2 - TRIAC
Switching mode
: isolated zero crossing type.
Rated current: from 50 mA to 1 A.
Rated voltage: from 24 V

RMS

to 240 V

RMS

-10% +15% (50-60

Hz).
Load type: resistive load only
I

2

t for external fuse: 128

Out 3 and 4
Function
: singularly programmable as:
- Control output
- Alarm output
- Event output.
- Servomotor drive (Out 3

s, out 4 t)

Type: Relay .
Relay type: SPST

Contact rating: 3 A @ 250 V on resistive load.
Notes:
1) The commons of the out 3 and 4 are connected together with

the same rear terminal.

2) When OUT 3 and 4 are used as independent relay outputs

the addition of the two currents must not exceed 3 A.

Servomotor output
Type
: Two relays with interlocked contact (Out 3 and 4).
Servomotor output type:
- Close loop
- Open loop with valve position indication
- Open loop.
Feedback potentiometer input: from 100

W to 10 kW.

Servomotor travel time: From 12 s to 3 minutes.
Servomotor dead band: From 1 % to 50 % of the feedback
span or of the valve travel time.
Analog outputs

Out 5 and 6
Function
: Programmable as
- Control output
- Analog retransmission of the measured value
- Analog retransmission of the operative set point.