Super Systems 20PQ User Manual

Page 110

Advertising
background image

106

The first FUNC pushbutton pressure modify the middle display
indication.
It will show:

- the time remaining to the end of the segment, if the

segment in progress is a ramp

- the operative set point, If the segment in progress is a soak.

The next FUNC pushbutton pressure regenerates the initial
middle display indication while the lower display indication will
be modified as follows:
a) Push the FUNC pusbutton again;

a.1) if a simple program is running, the lower display shows

"r." followed by the number of the cycle necessary to
complete the program.

a.2) if a linked program is running, the lower display shows

"L." followed by the number of the cycle necessary to
complete the linked program.

b) Push the FUNC pusbutton again; the lower display shows

"t.G." followed by the number of the tracking group pro-
grammed for the specific segment. The instrument will show
0 if no tracking group is assigned.

c) Push the FUNC pusbutton again; the lower display shows "u."

followed by the tracking above value programmed for the
specific segment. The instrument will show 0 if no tracking
band is assigned.

d) Push the FUNC pusbutton again; the lower display shows "d."

followed by the tracking below value programmed for the
specific segment. The instrument will show 0 if no tracking
band is assigned.

e) Push the FUNC pusbutton again; the lower display shows

"P.I.d." followed by the PID group programmed for the
specific segment.

f) Push the FUNC pusbutton again; the lower display shows "P."

followed by number of the program in progress.
When the instrument is in stand-by mode, the "P." indication
is followed by the program number selected by logic inputs (if
programmed and included between 1 and 99) or the last
executed program number.

g) Push the FUNC pusbutton again; the lower display shows "F."

followed by the number of free segments (segment not used).

h) Push the FUNC pusbutton again; the lower display shows

"A." followed by the current consumed by the load under test
when the load is in ON condition (see also "OUT failure
detection").

i) Push the FUNC pusbutton again; the lower display shows

" b." followed by the leakage current running in the load
under test when the load is in OFF condition (see also "OUT
failure detection").

XKP-1-C2.p65

10/30/01, 9:37 AM

106