CnF. 2

- OUT 5 retransmission full scale value
- [C.E10]

This parameter will be available only when Out 5 function
[C.E07] is configured as “PV.rt” or “SP.rt”
Range: From -1999 to 9999
NOTE: Decimal point is positioned as previously selected at

“CnF.1 - ñ.In.d” [C.d03])

- OUT 5 filter on the retransmitted value
- [C.E11]

This parameter will be available only when OUT 5 is configured
as process variable retransmission ("O5.Fn" [C.E07] is equal to
“PV.rt”).
Range: From 0 (no filter) to 8 seconds
NOTE: this is a first order digital filter applied to the
retransmitted output value.

- OUT 6 function - [C.E12]

Range: nonE = Output not used

ñAin

= Main control output (linear)

SECn = Secondary control output (linear)
PV.rt = Process variable retransmission
SP.rt = Operative set point retransmission

NOTE: When the option circuitry is not mounted the middle
display will show “no.Pr” (not present).

- OUT 6 range - [C.E13]

This parameter will be available only when Out 6 is configured
("O6.Fn" [C.E12] different from "nonE")
Range: 0-20

= 0

¸20 mA

4-20

= 4

¸20 mA

- OUT 6 retransmission initial scale value
- [C.E14]

This parameter will be available only when Out 6 function
[C.E12] is configured as “PV.rt” or “SP.rt”
Range: From -1999 to 9999
NOTES:
1) Decimal point is positioned as previously selected at “CnF.1 -

ñ.In.d” [C.d03])

2) The OUT 6 retransmission initial scale value can be higher

than OUT 6 retransmission full scale value [C.E.15].