Super Systems 20PQ User Manual

Page 148

Advertising
background image

144

STANDARD RANGES TABLE

LOGIC INPUTS
The instrument may be supplied with 11 logic inputs program-
mable as:
- Program selection
- RUN/HOLD mode selection
- ABORT function activation
- Auto/manual selection
- Output limiter activation
- Manual reset of the alarms (acknowledge)
- Reverse/direct control action
Input type: Contact closure (voltage free).
Active logic level: Close or open programmable.
Contact rating: 5 V DC, 2.5 mA

CURRENT TRANSFORMER INPUT FOR OUT FAILURE
DETECTION
The instruments equipped with this feature are capable, by
means of a CT, to detect and signal a possible failure of the line
driven by a control output programmed as a time proportioning
output (see "OUT failure detection").
Input range: 50 mA AC.
Scaling: programmable from 10 A to 100 A (with 1 A step).
Resolution:
- for full scale up to 25 A: 0.1 A.
- for full scale from 26 A to 100 A: 1 A
Minimum duration of the period (ON or OFF) to perform the
measurement
: 120 ms.

Input type

0 - 20 mA
4 - 20 mA

0 - 5 V
1 - 5 V
0 - 10 V
2 - 10 V

impedance

< 5

W

> 200 k

W

> 400 k

W

Accuracy

0.2 % + 1 digit

@ 25°C

XKP-1-C2.p65

10/30/01, 9:37 AM

144

Advertising