Super Systems 20PQ User Manual

Page 67

Advertising
background image

63

CnF. 6

- Out failure detection (OFD) - [C.I11]

This parameter will be available only when the option is fitted
and the main and/or the secondary output is configured as time
proportional control output
Range: nonE = Function not used

ñC.On = Set “Fd.Fn” to “ñC.On” when the load under test

is energized during the ON status of the main
output (relay energized or SSR output status 1).

ñC.OF = Set “Fd.Fn” to “ñC.OF” when the load under

test is energized during the OFF status of the
main output (relay de-energized or SSR output
status 0).

SC.On= Set “Fd.Fn” to “SC.On” when the load under test

is energized during the ON status of the second-
ary output (relay energized or SSR output status
1).

SC.OF= Set “Fd.Fn” to “SC.OF” when the load under test

is energized during the OFF status of the second-
ary output (relay de-energized or SSR output
status 0).

NOTE: When the option is not fitted the middle display will show
“no.Pr”

- Primary current of the current transformer
- [C.I12]

This parameter will be available only when “Fd.Fn” [C.I11] is
different from “nonE”
Range: From 10 A to 100 A

- Out failure detection - output assignment
- C.I13

This parameter will be available only when “Fd.Fn” [C.I11] is
different from “nonE”
Range: nonE = The "Out failure detection" alarm is signalled

only on display

OUt.1 = The "Out failure detection" alarm is signalled

on OUT 1

OUt.2 = The "Out failure detection" alarm is signalled on

OUT 2

OUt.3 = The "Out failure detection" alarm is signalled on

OUT 3

OUt.4 = The "Out failure detection" alarm is signalled on

OUT 4

NOTE: "Out failure detection "alarm annunciator cannot be
assigned to an output already configured as control output.