Configuration security code
The display will show:

Note: the middle display shows the current status of the
configuration security code ("0", "1" or "On").
By

s and t push-button, set "S.CnF" parameter as follows:

0

No protection (it is ever possible to modify all
configuration parameters);

1

ever protected (it is never possible to modify a
configuration parameter);

from 2 to 250 security code for configuration parameter

protection.

NOTE:

the selected value of a security code cannot be
displayed anymore and, coming back on the "S.CnF"
parameter, the display will show "On" when "S.CnF" is
different from 0 or 1, "0" when "S.CnF" is equal to 0,
"1" when "S.CnF" is equal to 1.
When the security code is forgotten, a new value can
be set.

Run time groups protected by security code
The display will show:

By this parameter it is possible to set if the run time group 2 will
be protected or not by the run time security code.
By

s and t push-button, set "Gr2" parameter as follows:

nO

No protection (it is always possible to modify run time
group 2 parameters)

Yes

the run time group 1 parameter modification will be
protected by security code.

Push the FUNC push-button; the instrument memorizes the new
setting and goes to the next parameter.

NOTES:1)This selection may be carried out only if a run time

security code has been set (from 2 to 250).

2) The above described selection may be repeated for

all groups of the run time mode.

XKP-1-C2.p65

10/30/01, 9:37 AM