Super Systems 20PQ User Manual

Page 35

Advertising
background image

31

CnF. 1

8 = TC S

From - 50 to 1760

°C

9 = TC R

From - 50 to 1760

°C

10 = TC B

From

0 to 1820

°C

11 = TC G (or W)

From

0 to 2300

°C

12 = TC D (or W3)

From

0 to 2300

°C

13 = TC C (or W5)

From

0 to 2300

°C

14 = TC Ni-Ni18%Mo From

0 to 1100

°C

* 15 = RTD Pt100

From -200 to

850

°C

16 = TC L

From -150 to 1650

°F

17 = TC J

From -150 to 1830

°F

18 = TC K

From -150 to 2500

°F

19 = TC T

From -330 to

750

°F

20 = TC U

From -330 to 1110

°F

21 = TC E

From -150 to 1470

°F

22 = TC N

From -150 to 2550

°F

23 = TC S

From - 60 to 3200

°F

24 = TC R

From - 60 to 3200

°F

25 = TC B

From

32 to 3300

°F

26 = TC G ( or W)

From

0 to 4170

°F

27 = TC D (or W3)

From

0 to 4170

°F

28 = TC C (or W5)

From

0 to 4170

°F

29 = TC Ni-Ni18%Mo From

0 to 2000

°F

* 30 = RTD Pt100

From -330 to 1560

°F

31 = Linear

From

0 to

20 mA

32 = Linear

From

4 to

20 mA

33 = Linear

From

0 to

5

V

34 = Linear

From

1 to

5

V

35 = Linear

From

0 to

10

V

36 = Linear

From

2 to

10

V

37 = Linear

From

0 to

60 mV

38 = Linear

From

12 to

60 mV

* For these ranges it is possible to select a read-out with one

decimal figure but the instrument could not display a measure
lower than -199.9 or higher than 999.9 and the input range
will be limited by it.

NOTES:
1) When a linear input is selected, the instrument automatically

sets the "readout initial scale value" [C.d05] equal to 0 and
the "readout full scale value" [C.d06] equal to 4000

2) When input type has been changed, the instrument

automatically forces:

- the "ñ.In.L" [C.d05], "SS.th" [C.I09] and "brG.L" [C.I03]

parameters to the new initial scale value,

- the "ñ.In.H" [C.d06] and "brG.H" [C.I04] parameter to the

new full scale value and

- the "ñ.In.d" [C.d03] parameter to "no decimal figure".

XKP-1-C2.p65

10/30/01, 9:37 AM

31