Super Systems 20PQ User Manual

Page 74

Advertising
background image

70

Gr. 2

Run time group 2 [r.bxx]
COMMAND

- Programmer/controller mode selection
- [r.b01]

This parameter can be modified only when no program is
running.
Range: YES= the device will be operative as programmer

nO = the device will be operative as controller

- Main set point - [r.b02]

This parameter is available when the instrument is in controller
mode only.
Range: from rL (set point low limit [rE.12]) to rH set point high

limit [rE.13]).

- SMART function - [r.b03]

This parameter is available when the instrument operates in
controller mode, at least one control output is configured and
SMART function is enabled (“Sñ.Fn” [C.G01]= “Enb”)
Range: OFF = SMART algorithm is deactivated

ON = SMART algorithm is activated

Note: if the transfert from controller to programmer mode is
required when the SMART function is active, the instrument
automatically disables the SMART function.

- Output Power OFF mode - [r.b04]

This parameter is available only when no program is running.
Range: YES = Output Power OFF mode is active

No = Output Power OFF mode is deactivated

- Program selection for clock start - [r.b05]

This parameter is available when the clock option is fitted and
enabled ("En.Ck" [CI.14] parameter is different from "nonE").
Range: nonE

= Clock start disabled

XKP-1-C2.p65

10/30/01, 9:37 AM

70

Advertising