CnF. 3

- Main output auxiliary conditioning - [C.F11]

This parameter will be available only when main control output is
configured and “ñC.Cn” ("Main control output conditioning"
[C.F06]) is different from “norñ”.
Range: bEFr = The functions listed at Note (*) are calculated

before to apply the action selected by “ñC.Cn”
("Main control output conditioning" [C.F06])
parameter.

AFtr

= The functions listed at Note (*) are calculated

after to apply the action selected by “ñC.Cn”
(“Main control output conditioning” [C.F06])
parameter.

Note (*)
- "Main control output limiters" - for more details see [r.E04]

and [r.E05] parameters.

- "Main control output max rate of rise" (see [r.E06]).
- "Control output display value" - for more details see "Display

function during programmer mode" paragraph at pag. 106
and [C.F07], [C.F08], [C.F09] and [C.F10] parameters.

- "Threshold for alarm on control output value" - for more

details see [r.F01], [r.F05] [r.F09] and [r.F13] parameters.

- The control output value displayed by bargraph.

- Secondary control output conditioning
- [C.F12]

This parameter will be available only when secondary control
output is configured.
Range: norñ

= The control output is calculated by the PID

CñPL = The control output is complemented (100-PID

calculated value)

Ouic

= The control output is conditioned to match a

“QUICK OPENING” flow characteristic

Eou

= The control output is conditioned to match an

“EQUAL PERCENTAGE” flow characteristic

For more details see also NOTE about output conditioning at
page 44.