Alarm setup, Larm, Etup – Super Systems 9205 Series User Manual

Page 104

Advertising
background image

Series 9205 Operations Manual Rev A

103

Alarm Setup

The 9205 controller can be configured to use

three (3) different alarms, and a Thermocouple

Check. Each of the alarms consists of an alarm

setpoint, alarm type, alarm hysteresis, smart

alarm, ON delay time, 0 SP blocks alarm value,

Burnoff/Impedance inhibits alarm, Inhibit

source, and disable on open input. The alarms

come from the factory with a default

configuration dependent on the application but

also can be modified prior to shipment to your

facility or in the field by a supervisor. See the

section Appendix E – Factory Default Settings for

the 9205 Controller for more information on

factory default settings for the alarms.

Setpoint

This value is the setpoint for the alarm. Clicking on this value will display an input box from which the user

can select a new value. The range is from –9999 to 9999.

Alarm Type

This value is the type of alarms used. Clicking on this value will display an input box with two (2) drop-down

lists from which the user can select a new value.

The values in the first (top) list box are:

PV 1 Value

PV 2 Value

PV 3 Value

N/A

Input 1 Value

Input 2 Value

Input 3 Value

PO1 Value

PO2 Value

PO3 Value

The values in the second (bottom) list box are:

Process High

Process Low

Out of Band

In Band

Outside Deviation

Within Deviation

Band alarm works by looking at a value above and below setpoint. Deviation alarm works

by looking at a value either above or below (based upon the setpoint value the user has

entered). A few examples would probably be best to explain how to set these up properly.

Hysteresis

This value is the Hysteresis value. The Hysteresis is a set number that works with the alarm to help control

a motor or pump longer to reach a set amount to come back into band before it will shut off motor or pump.

Advertising
This manual is related to the following products: