Generic instrument setups, Configure generic instruments, Eneric – Super Systems 9205 Series User Manual

Page 125: Nstrument, Etups

Advertising
background image

Series 9205 Operations Manual Rev A

124

Generic Instrument Setups

The generic instrument’s data will be stored in

certain registers on the host instrument, such

as the 9205 controller. Each instrument is

allotted a certain set of registers, starting with

register 1000. To determine the beginning

register, use the following calculation: (100 *

generic instrument’s number (1 – 16)) + 900.

Therefore, instrument 1 would begin at

register 1000: (100 * 1) + 900. Instrument 7

would begin at register 1600: (100 * 7) + 900. Each instrument is allotted 100 registers, therefore,

instrument 1’s allotment is from register 1000 to 1099 on the 9205 controller, instrument 2’s allotment is

from register 1100 to 1199 on the 9205 controller, etc.

The

Generic Instrument Setups

menu is split into three parts: Configure Generic Instruments, Configure IP

Addresses, and Configure Block Writes.

Configure Generic Instruments

This screen is where the user can

configure the main sections for

each generic instrument. The

drop-down box in the top left will

select the generic instrument to

set up. The options are:

Instrument 1 – Instrument 16.

The three reads can be set up in

the grid in the top of the form.

The Instrument Register field will

be the register in the 9205

controller. The range is 0 – 32767.

The Count field will be the number of successive registers to read. The range is 0 – 100. The Storage Offset

field will be the offset in the generic instruments registers (1000 – 1099 for Instrument 1, 1100 to 1199 for

Instrument 2, etc). The range is 0 – 99.

The setup for the PV (Process Variable), SP (Setpoint), and

Out (Output) can be done in the grid in the bottom of the form.

The Offset field is the instrument’s offset. The range is 0 –

32767. The Instrument Register field is the register in the

9205 controller. The range is 0 – 32767. The Input Type field

will determine what kind of type the value will be. The

options are: Integer, Big Endian, Big Endian Byte Swap, Little

Endian, or Little Endian Byte Swap. The Exponent field will

determine if there is an exponent value. Checking the

checkbox will indicate that the Scaler is a power of 10. The

Input Scaler field can then be a positive or negative value in

the range -31 to +31. The Output Type will determine what

kind of the output value will be. The options are: Integer, Big

Endian, Big Endian Byte Swap, Little Endian, or Little Endian

Byte Swap. The Exponent field will determine if there is an

exponent value. Checking the checkbox will indicate that the

Scaler is a power of 10. The Output Scaler field can then be a

positive or negative value in the range -31 to +31.

NOTE:

Exponent values affect only floating point values.

Advertising
This manual is related to the following products: