Super Systems 9205 Series User Manual

Page 46

Advertising
background image

Series 9205 Operations Manual Rev A

45

If it is set for an input, it will preload the timer but wait until it sees the input configured go high before it

starts timing. The options are: On Recipe Opcode (

QUENCH

Opcode), Input 1 – Input 31.

Quench Hold Event

This option will determine which event will hold the quench cycle. It is used to hold the quench timer with

an external device. If the input that is configured turns on then the quench timer will go into a hold mode.

The list of possible values is: 0 – 15.

Quench Transfer Time Configuration

This option will allow the user to set what will trigger the transfer from the quench cycle. The options are:

Event 2 Active Time, or Event 1 Active to Event 2 Active.

Cascade Inhibit

Note: This field is only applicable if the controller is in Cascade mode

. This will turn cascade control on or

off. When inhibit = enabled, the 9205 functions as a multi-loop controller with three control loops. The

options are: enabled or disabled.

PV Difference Cutback

Note: This field is only applicable if the controller is in Cascade Mode

. This is used with the Cascade Lower

Range EOPV and Cascade Upper Range EOPV to limit the absolute % output of the furnace loop. This will

turn the PV difference cutback feature on or off. The options are: enabled or disabled.

Cascade Lower Range EOPV

Note: This field is only applicable if the controller is in Cascade Mode

. This is the cascade lower range end

of PV difference. This is used with the PV Difference Cutback and Cascade Upper Range EOPV to limit the

absolute % output of the furnace loop. Between the lower range EPOV and the upper range EOPV, there is

a linear interpolation from 0 to the loop 2 output maximum (usually 100 %) that determines the maximum

% output for the furnace loop. The range is -300 to 10000.

Cascade Upper Range EOPV

Note: This field is only applicable if the controller is in Cascade Mode

. This is the cascade upper range end

of PV difference. This is used with the Cascade Lower Range EOPV and PV Difference Cutback to limit the

absolute % output of the furnace loop. Between the lower range EPOV and the upper range EOPV, there is

a linear interpolation from 0 to the loop 2 output maximum (usually 100 %) that determines the maximum

% output for the furnace loop. The range is -300 to 10000.

Example: With the Lower EOPV set to 10 and the Upper EOPV set to 110, if the load PV is 1700 and the

furnace PV is 1710, the full 100% output is available. If the load PV is 1600 and the furnace PV is 1710, the

furnace output will not go above 0%. If the load PV is 1655 and the furnace PV is 1710, the maximum output

for the furnace loop will be limited to 55%: (1710 – 1655)/(110-10) * (1.0).

Multiloop Display

This option allows the user to decide which combination of loops will be displayed on the default status

screen. The choices are:

No display

Loop 1, Loop 2

Loop 2, Loop 3

Loop 1

Loop 3

Loop 1, Loop 2, Loop 3

Loop 2

Loop 1, Loop 3

The Return button will return the user to the menu screen.

Advertising
This manual is related to the following products: