Series 9205 Operations Manual Rev A

114

Delay Time

This is the time in seconds that will pass once the TCs go out of band before an alarm is activated to prevent

excessive, unnecessary alarming. The range is 0 to 3200 seconds.

TC Selection

To change this option from TC 1, the Select Mode must be in manual.

Select Mode

This allows the operator to choose whether the highest or lowest TC will automatically be chosen, or

whether it will be manually chosen by the operator. The options are highest, lowest, and manual.

NOTE: If the 9205 has redundant TC active, then digital inputs 2 and 3 can manually override the system and

force the selected TC to be TC 1 if input 1 is active or TC 2 if TC 2 is active. If both input 1 and input 2 are

active, input 1 will take precedence and make TC 1 active.

Event Control

The Event control provides the user manual

control of actual event outputs. This is useful

when testing wiring and field devices.

Programmer 1 and Programmer 2 event

outputs can be controlled. The Programmer

number is selected with the Programmer

drop-down box under the menu box in

Configurator.

Hold Instrument Number

Clicking on this value will display an input box

from which the user can select a new value.

The range is 0 to 25.

Hold Minimum PV

Clicking on this value will display an input box

from which the user can select a new value.

The range is 0 to 4000.

Hold Maximum PV

Clicking on this value will display an input box

from which the user can select a new value.

The range is 0 to 4000.

Event for Program Run

Clicking on this value will display an input box from which the user can select a new value. The range is -0

to 15. A value of -1 will disable this option.

Event for Program Reset

Clicking on this value will display an input box from which the user can select a new value. The range is -0

to 15. A value of -1 will disable this option.

Input Event 0 – Input Event 15

The input box for these events has two drop-down lists. The top list contains active and inactive, and the

bottom list contains closed and open.