Zone assignments – Super Systems 9205 Series User Manual

Page 42

Advertising
background image

Series 9205 Operations Manual Rev A

41

Zone Assignments

WARNING: This screen should not be changed

without consulting SSi at (513) 772-0060.

*Slave Instrument Setup must be configured prior to

Zone Assignment setup

The zone assignment feature allows the Series 9205

program to change set points on all instruments of a

multi-zone furnace. The Series 9205 has up to five

temperature and atmosphere zone assignments

available (Zone Assignment 1 – Zone Assignment 5).

Typically, the first zone is configured to the

programmer’s atmosphere or temperature

instrument. That is the master set point that will be propagated to the other configured zone instrument

set points on set point change. For example, the user may want to set 4 temperature zones from a recipe

where the programmer temperature instrument is loop 2. In this case, zone 1 would be configured as loop

2. Subsequent zones would be configured as previously configured slave temperature controllers.

If the

ZONE_OFF

(Zone Offset) opcode had been used in the program, the set point sent to the specified

zone instrument would have the offset added. For example, a 3-zone pit furnace, where the bottom zone

usually has a higher set point. The middle zone and the top zone usually have a lower set point. The bottom

zone temperature controller is assigned to zone 1, the middle temperature controllers to zone 2, and the

top zone controller to zone 3.

If the first three steps of a program are as shown below, then the bottom zone set point is 1775, the middle

zone is 1750, and the top zone is 1800.

Step

Opcode

Temperature

Option

1

ZONE_OFF

25

Zone 1

2

ZONE_OFF

50

Zone 3

3

SETPT

1750

The first step sets the offset for zone 1 to 25 degrees; therefore, the bottom zone controller would be sent a

set point of 1775 when step 3 is executed. Likewise step 2 sets the offset for zone 3 to 50 degrees. The top

zone then receives a set point of 1800. The middle zone controller would receive the 1750. The temperature

controller displayed on the Status Display is instrument #2. If instrument #2 were the top zone controller

then the Status Display would show the 1800-degree set point.

When using the multi-zone offset feature, the temperature controller assigned as instruments 1 and 2

should be in zones that will not be offset.

Atm Source

This will allow the user to set the atmosphere instrument for the zone assignment. The options are

Loop 1

Instrument 5

Instrument 12

Instrument 19

Loop 2

Instrument 6

Instrument 13

Instrument 20

Loop 3

Instrument 7

Instrument 14

Instrument 21

Instrument 1

Instrument 8

Instrument 15

Instrument 22

Instrument 2

Instrument 9

Instrument 16

Instrument 23

Instrument 3

Instrument 10

Instrument 17

Instrument 24

Instrument 4

Instrument 11

Instrument 18

Instrument 25

Advertising
This manual is related to the following products: