Series 9205 Operations Manual Rev A

156

This opcode is a guaranteed low short delay opcode. The temperature process value must be above the

lower limit deviation band to allow the delay timer to run. If the temperature process value goes out of the

deviation band, then the delay timer will stop and wait until the temperature process value comes back into

the deviation band before starting up again.

The Delay Time is from 1 – 500 seconds.

GLSOAK

N/A

Wait Limit

Soak Time

This is a guaranteed soak low opcode. The temperature process value must be above the lower limit

deviation band to allow the soak timer to run. If the temperature process value goes out of the deviation

band, then the soak timer will stop and wait until the temperature process value comes back into the

deviation band before starting up again.

The Wait Limit is the wait time, in Hours: Minutes format, for the wait limit. The Hours range from 0 – 533,

and the Minutes range from 0 – 59.

The Soak time is the total time, in Hours:Minutes format, for the soak to run. The Hours range from 0 –

166, and the Minutes range from 0 – 59.

The band limit can be changed by the

SET_WAIT

opcode.

GLZDELAY

N/A

N/A

Delay Time

This is a guaranteed low short delay opcode for a zone. The temperature process value must be below the

deviation band to allow the delay timer to run. If the temperature process value goes out of the deviation

band, then the delay timer will stop and wait until the temperature process value comes back into the

deviation band before starting up again.

The Delay Time is from 1 – 500 seconds.

GLZSOAK

N/A

Wait Limit

Soak Time

This is a guaranteed soak low opcode for a zone. The temperature process value must be above the lower

limit deviation band to allow the soak timer to run. If the temperature process value goes out of the

deviation band, then the soak timer will stop and wait until the temperature process value comes back into

the deviation band before starting up again.

The Wait Limit is the wait time, in Hours: Minutes format, for the wait limit. The Hours range from 0 – 533,

and the Minutes range from 0 – 59.

The Soak time is the total time, in Hours:Minutes format, for the soak to run. The Hours range from 0 –

166, and the Minutes range from 0 – 59.

The band limit can be changed by the

SET_WAIT

opcode.

GOSUB

N/A

N/A

Recipe Number

The go to subroutine opcode is used to call a program to run and then return to the calling program. This is

used to execute standard routines that can be used by many programs.

GOSUBs

can be stacked up to eight

(8) levels.

The Recipe Number is the recipe (program) to run. The range is 1 – 300.

GRAMP

Temperature Setpoint

Atmosphere Setpoint

Time

This is a guaranteed ramp opcode. The process value must be within the deviation band to allow the ramp

timer to run. If the process value goes out of the deviation band, then the ramp timer will stop and wait

until the process value comes back into the deviation band before starting up again.

The Temperature Setpoint is the setpoint to send for the temperature process variable. The range is -301

(disable) – 30000.

The Atmosphere setpoint is the setpoint to send for the atmosphere process variable. The range is -0.01 to

99.99.