Series 9205 Operations Manual Rev A

76

Analog Input Correction Curves

This option allows the user to edit a curve on an input 1,2,

or 3 at a specific temperature point. Select the

appropriate curve and press Edit to customize specific

points.

Select the point to be changed, and press Edit again.

Input the correct Temperature and Error, and press OK

to save.

Instrument Calculation

The Instrument Calculation menu allows programming

code-like lines to be executed at a variable time

interval per step.

Note: It is important to contact Super

Systems at (513) 772-0060 before creating or modifying

any Instrument Calculation customization

.

General Description

The Instrument Calculation allows for fifty (50) lines of

program and fifty (50) program variables. Program

variables allow for storage on intermediate results of

calculations.

A program variable is designated by a v followed by a number from 0 to the number of variables – 1.

A Lower or Upper case “V” is valid, as well as leading zeroes. The following are all considered the same

variable: V3, v3, v0003.

The 9205’s Modbus registers can be used as input variables in the equations without restriction. To protect

the instrument, Modbus registers are restricted as output registers.

Modbus registers are designated by an upper or lower case “M” followed by a number.

Note – The standard Modbus routine is called to retrieve the Modbus variable, therefore a 0x8000 (-32768)

will be returned for an invalid register

.

Note – Modbus registers are stored with integer values, so adjustments will need to be made for decimal

values

.

If the instrument can have external analog input boards, or the instrument is a Video Recorder or DAQ,

these inputs can be accessed directly as A1 through A40. By using the “A” designation, the Modbus register

number is not needed and the variable is scaled to the correct value (decimals included) based on the input

type specified.

In a Video Recorder, the slave instrument data slots can be defined as variables D1 through D32. D31 and

D32 are extra slots and have no restrictions as output variables. D1 through D30 are shared with the first

ten (10) slave instruments in groups of three (3) – PV, SP, PO – and caution should be used when assigning

as outputs.

A line in the program of the instrument calculation must start with a variable or a keyword.

Variables must be followed by an equal sign (=) and then an expression. The expression can be a simple

assignment (V1 = 3) or a variable operation variable as described below (V1 = M225 * 0.1).

Keywords

MUST

be entered in capital letters only.

The list of valid keywords is: IF, ELSE, ENDIF, QUE, RLY, and END.

“IF” must be followed by an expression which is a variable, relationship operator, then variable.

The list of valid relationship operators is: > (Greater Than), < (Less Than). = (Equals), >= (Greater Than or

Equal To), <= (Less Than or Equal To), != (Not Equal To), and == (Equal To).

Note – The “=” and “==”

relationship operators are identical

.

The list of valid bitwise operators is: & (AND), | (OR), ^ (XOR), << (Left Shift), and >> (Right Shift).

The result of the “IF” relationship test determines if the lines following the “IF” statement will be executed

or not.

The “ELSE” and “ENDIF” must be on a line by themselves. “ELSE” will toggle the program based on the

result of the “IF” test. “ENDIF” will close out the “IF”.