Redundant TC Setup

This option allows the operator to choose which TC to control

in a redundant TC setup. The redundant TC setup allows for

two thermocouples to be used and measured from. This

option can be configured so that the higher or lower is

automatically selected or in manual mode so that the

operator can choose which TC to use.

Band

The Band lets the user set how far apart the values of the TCs

in the redundant setup can be before an alarm is activated.

The alarm can be assigned under the Relay Assignment

menu option. The range for this is -4000 to 4000.

Delay Time

This is the time in seconds that will pass once the TCs go out of band before an alarm is activated to prevent

excessive, unnecessary alarming. The range is 0 to 3200 seconds.

TC Selection

To change this option from TC 1, the select mode must be in manual.

Select Mode

This allows the operator to choose whether the highest or lowest TC will automatically be chosen, or

whether it will be manually chosen by the operator. The options are highest, lowest, and manual.

NOTE: If the 9205 has redundant TC active, then digital inputs 2 and 3 can manually override the system and

force the selected TC to be TC 1 if input 1 is active or TC 2 if TC 2 is active. If both input 1 and input 2 are

active, input 1 will take precedence and make TC 1 active.

Event Hold/Reset

The Event Hold/Reset menu option provides the user manual

control of actual event outputs. This is useful when testing

wiring and field devices.

Hold Instrument Number

Clicking on this value will display an input box from which the

user can select a new value. The range is 0 to 25.

Hold Minimum PV

Clicking on this value will display an input box from which the

user can select a new value. The range is -32768 to 32767.

Hold Maximum PV

Clicking on this value will display an input box from which the user can select a new value. The range is -

32768 to 32767.

Event for Program Run
Clicking on this value will display an input box from which the user can select a new value. The range is –1
(Disable) to 15.