Series 9205 Operations Manual Rev A

84

Click on the OK button to set the new value, or click on the Cancel button to cancel.

Burnoff Recovery Wait Time:

The amount of time allotted to allow the probe measurements to return to a stable, accurate range after

the burnoff is complete. This is measured in seconds. The control output is held until this time is elapsed.

Clicking on the value will allow the user to change the value.

Burnoff Interval:

This is the amount of time between the beginning of one burnoff and the beginning of the next scheduled

burnoff, in minutes. Default time for the instrument is 720 minutes (12 hours). However, the amount of

time between burnoffs should be determined by the application.

Burnoff Minimum Millivolts:

The minimum measured millivolt tolerance of the probe required to start a burnoff. Clicking on the value

will allow the user to change the value. SSi recommends the millivolt value gets down to 200 mV.

Burnoff Maximum Temperature:

The maximum measured temperature allowed during a burnoff. If the temperature value is exceeded

the

burnoff will stop

. This is done to help maintain the life and the accuracy of your probe. SSi recommends a

value of 1800 degrees. Clicking on the value will allow the user to change the value.

Digital IN 4 Assignment:

The value for the digital input 4 assignment. Clicking on the value will allow the user to change the value,

which can be either event or start BO.

Burnoff Minimum Millivolts Alarm Setpoint:

The minimum millivolt value that must be reached in order for the “Insufficient mV drop during BO” alarm

not to be generated. If the millivolt value does not drop below the minimum, the alarm will be generated.

Burnoff Maximum Temperature Rise Limit:

The maximum number of degrees that the temperature is allowed to increase before the “Excessive TC rise

during BO” alarm is generated.