Series 9205 Operations Manual Rev A

88

Setpoint Upper Limit

This is the upper limit for the setpoint. The range is –100 to 100.

PV Source

The options for PV Source are either Internal or External. If External is selected, the loop’s PV must be

written by an external source. Selecting Internal will continue normal operation where the source is

determined by the PID loop and the PV type.

Minimum Forward On Time (sec)

This setting specifies the minimum number of seconds for which output must be positive (heating) before

the control is turned off. The maximum value for this setting is 100.

Minimum Forward Off Time (sec)

This setting specifies the minimum number of seconds for which the control must be off after heat is

applied. The maximum value for this setting is 100.

Minimum Reverse On Time (sec)

This setting specifies the minimum number of seconds for which output must be negative (cooling) before

the control is turned off. The maximum value for this setting is 100.

Minimum Reverse Off Time (sec)

This setting specifies the minimum number of seconds for which the control must be off after cooling is

applied. The maximum value for this setting is 100.

Positive Output Accumulator

The Positive Output Accumulator is the sum of the positive outputs (given in percentages up to one decimal

place) measured each second. Therefore, if the following outputs are recorded over five seconds:

Output (in %)

Second Passed

100.0

1

99.0

2

99.0

3

98.0

4

97.0

5

Then the value for the Positive Output Accumulator after five seconds will be (100.0 + 99.0 + 99.0 + 98.0 +

97.0) or 493.0.

To reset the Positive Output Accumulator, simply click Edit while the Positive Output Accumulator is

highlighted and confirm the reset. This will cause the Positive Output Accumulator to be reset to zero and

start accumulating values again from that point.

Negative Output Accumulator

The Negative Output Accumulator is the sum of the negative outputs (given in percentages up to one

decimal place) measured each second. The sum of the negative values is expressed as a positive value. This

means that, if an output of -50% is recorded after one second, a value of 50 will be added to the Negative

Output Accumulator. Similarly, if the following outputs are recorded over five seconds:

Output (in %)

Seconds Passed

-20.0

1

-20.0

2

-21.0

3

-21.0

4

-22.0

5