Series 9205 Operations Manual Rev A

122

C

40mV

E

80mV

J

80mV

K

80mV

N

80mV

NNM

80mV

R

40mV

S

20mV

T

20mV

Click the Done button to close the screen down.

Auxiliary Input Offset Correction

This menu option will allow the user to enter offsets

for the auxiliary inputs and apply any correction curves

as needed. The offset can be in degrees + or -, and it

is typically used to compensate for incorrect T/C wires.

Enable Offsets for SSi AIB

This will enable the use of offsets for any analog input

boards. The options are: Yes or No.

Input 1 – Input 40

This is where the actual offsets will be entered for

each input. The range is -50.0 – 50.0.

Input 0 Correction – Input 39 Correction

This is where any correction curve can be applied for

each input.

Note – The input names for the corrections

are offset by 1, so Input 0 is actually Input 1, Input 39 is

actually Input 40, etc

. The options are: Not Used,

Curve 1, Curve 2, or Curve 3.