The Time is the total time for the program to reach the desired setpoint(s), in Hours:Minutes format. The

Hours range from 0 – 166, and the Minutes range from 0 – 59.

The band limit can be changed by the

SET_WAIT

opcode.

GTCINQDEL

Delay Time

T/C

Option

This is a guaranteed TC inquiry short delay opcode. It is used to verify that all active thermocouples are

within the set wait limits around the setpoint for the user defined time period.

The Delay Time is the time in seconds before checking the T/Cs. The range is 0 – 500.

The T/C is the Control T/C or Load T/C to use. The options are: Control T/C, T/C 1 – T/C 24.

The Option will allow the user to wait for the T/Cs to come within the set wait limits around the setpoint.

The options are: Wait, Wait Up, or Wait Down.

GZ_SOAK

N/A

N/A

Soak Time

This is a guaranteed soak opcode for a zone. The temperature process value must be within the deviation

band to allow the soak timer to run. If the temperature process value goes out of the deviation band, then

the soak timer will stop and wait until the temperature process value comes back into the deviation band

before starting up again.

The Soak time is the total time, in Hours:Minutes format, for the soak to run. The Hours range from 0 –

166, and the Minutes range from 0 – 59.

The band limit can be changed by the

SET_WAIT

opcode.

GZDELAY

N/A

N/A

Delay Time

This is a guaranteed short delay opcode for a zone. The temperature process value must be within the

deviation band to allow the delay timer to run. If the temperature process value goes out of the deviation

band, then the soak timer will stop and wait until the temperature process value comes back into the

deviation band before starting up again.

The Delay Time is from 1 – 500 seconds.

GZRAMP

Temperature Setpoint

Atmosphere Setpoint

Time

This is a guaranteed ramp opcode for a zone. The process value must be within the deviation band to allow

the ramp timer to run. If the temperature process value goes out of the deviation band, then the ramp

timer will stop and wait until the temperature process value comes back into the deviation band before

starting up again.

The Temperature Setpoint is the setpoint to send for the temperature process variable. The range is -301

(disable) to 30000.

The Time is the total time for the program to reach the desired setpoint(s), in Hours:Minutes format. The

Hours range from 0 – 166, and the Minutes range from 0 – 59.

The band limit can be changed by the

SET_WAIT

opcode.

HIGH_AL

Temperature Setpoint

Atmosphere Setpoint

N/A

This opcode is used to enable a high limit alarm on the temperature or atmosphere process. This alarm

remains active until the program ends.

The Temperature Setpoint is the setpoint to send for the temperature process variable. The range is -301

(disable) to 30000.

The Atmosphere Setpoint is the setpoint to send for the atmosphere process variable. The range is -0.01

(disable) to 99.99.

HIGH_PO

Temperature PO Value

Atmosphere PO Value

N/A