Plc data mapping, Analog input correction curves, Instrument calculation – Super Systems 9205 Series User Manual

Page 129: Apping, Nalog, Nput, Orrection, Urves, Nstrument, Alculation

Advertising
background image

Series 9205 Operations Manual Rev A

128

PLC Data Mapping

This option allows the user to custom map data from

registers inside the PLC to the registers in the

controller, and vice versa. The 9205 registers for

mapping use a hexadecimal number to decode, so

4100hex will get instrument 1 offset 0. 4101hex will get

an instrument 1 offset 1

NOTE: Convert the Hexadecimal value to Decimal value

before entering it into the 9205.

For example: 4400Hex is 17408 Decimal.


Analog Input Correction Curves

This option allows the
user to edit a curve on an
input 1,2, or 3 at a
specific temperature
point. Select the
appropriate curve and
Click to edit. Input the
temperature and the
error.

Instrument Calculation

The Instrument Calculation menu allows programming code-like lines to be executed at a variable time

interval per step.

Note – It is important to contact Super Systems at (513) 772-0060 before creating or

modifying any Instrument Calculation customization

.

General Description

The Instrument Calculation allows for fifty (50) lines of program and fifty (50) program variables. Program

variables allow for storage on intermediate results of calculations.

A program variable is designated by a v followed by a number from 0 to the number of variables – 1.

A Lower or Upper case “V” is valid, as well as leading zeroes. The following are all considered the same

variable: V3, v3, v0003.

The 9205’s Modbus registers can be used as input variables in the equations without restriction. To protect

the instrument, Modbus registers are restricted as output registers.

Modbus registers are designated by an upper or lower case “M” followed by a number.

Note – The standard Modbus routine is called to retrieve the Modbus variable, therefore a 0x8000 (-32768)

will be returned for an invalid register

.

Note – Modbus registers are stored with integer values, so adjustments will need to be made for decimal

values

.

If the instrument can have external analog input boards, or the instrument is a Video Recorder or DAQ,

these inputs can be accessed directly as A1 through A40. By using the “A” designation, the Modbus register

Advertising
This manual is related to the following products: