Super Systems 9205 Series User Manual

Page 48

Advertising
background image

Series 9205 Operations Manual Rev A

47

Band, Normally Closed

Deviation, Normally Open

Deviation, Normally Closed

Band alarm works by looking at a value above and below setpoint. Deviation alarm works

by looking at a value either above or below (based upon the setpoint value the user has

entered). A few examples would probably be best to explain how to set these up properly.

Hysteresis

This value is the Hysteresis value. The Hysteresis is a set number that works with the alarm to help control

a motor or pump longer to reach a set amount to come back into band before it will shut off motor or pump.

Example: Using quench oil as an example, suppose the SP is 200 °F. The alarm is set as a deviation of +10

°F. At 210 °F, the alarm is active and the pump will run to cool the oil. With a hysteresis of 8 °F, the alarm

and pump will turn off at 202 °F. It will turn back on when it is 10 °F above setpoint. If the setpoint is still

200 °F, then at 210 °F, it will turn on again.

Clicking on this value will display an input box from which the user can select a new value. The range is

from -32767 to 32767.

Smart Alarm

This value is a display of the Smart Alarm status. A smart alarm is an alarm that works with a Process

Variable (PV), and, when enabled, it will not be active until the PV is within band of the setpoint. The alarm

sounding - if active - will be disabled until within the SP band. When it is in band, the alarm will go active

unless on delay time is set.

Example: If the SP is 1700 °F and the band is 10 °F, the alarm will not be active until the PV reaches 1690

°F. The value can be either disabled or enabled.

ON Delay Time

This value is the On Delay Time for the alarm. Clicking on this value will display an input box from which

the user can select a new value. The range is from -32767 to 32767.

0 Setpoint Blocks Alarm

This value will allow a 0 setpoint to block an alarm. The options are either No or Yes.

BO/Impedance inhibits alarm

If BO/Impedance inhibits alarm is turned to Yes, no alarm will sound if the carbon percentage drops

because of a burnoff.

Inhibit Source

Alarms can be inhibited in order to prevent false or unnecessary alarm notifications. The Inhibit Source

option will allow the user to set the source of the inhibit signal. The options are: None, Input 1 – Input 4,

Soak timer inactive (The alarm will not happen if the furnace is in a soak if this option is selected), and .

Input 6 – Input 15.

Disable on open input

An alarm can be disabled when an input the open in order to avoid false or unnecessary alarms. This option

will allow the user to specify if the alarm is disabled when the input is open. The options are either no or

yes.

The Return button will return the user to the menu screen.

Advertising
This manual is related to the following products: