Series 9205 Operations Manual Rev A

120

box. If the input was showing 1748°F, while sourcing 1750°F, then the “Offset” difference would be 2°F to

bring the display back up to 1750°F.

Note: The current cold junction value is for display purposes. It will need to be used when determining the

cold junction offset. You will need to add to or subtract from the displayed value the amount of difference,

example 2°F difference being applied to 90 (like in the image) your new CJ value will need to be 92°F.

When ready click on the Calibrate button to begin the calibration.

Wait 120 seconds and verify with a source calibration device with the correct T/C type. Note: During a

normal calibration procedure, the user should zero and span calibrate all of the inputs first and then

perform a cold junction calibration, if necessary.

Click on the Done button when finished. You will then be able to verify on the main display your sourced

value when compared to the actual reading in Configurator.

Full Calibration

NOTE: Full calibration is performed by SSi. The below information is provided for reference only.

The

Calibration

screen for the Full Calibration menu option is identical in function and layout to the User

Calibration’s

Calibration

screen. The only difference is the Full Calibration’s

Calibration

screen contains

more screens. This list of screens is listed below in sequential order. Screens only found in the Full

Calibration menu option are displayed in

Italics

. Screens only found in the User Calibration menu option

are displayed in bold.

1.

Cold Junction

2.

Zero/Span Input 0/Range 0

3.

Zero/Span Input 0/Range 1

4.

Zero/Span Input 0/Range 2

5.

Zero/Span Input 0/Range 3

6.

Zero/Span Input 1/Range 0

7.

Zero/Span Input 1/Range 1

8.

Zero/Span Input 1/Range 2

9.

Zero/Span Input 1/Range 3

10.

Zero/Span Input 2/Range 0

11.

Zero/Span Input 2/Range 1

12.

Zero/Span Input 2/Range 2

13.

Zero/Span Input 2/Range 3

14.

Zero/Span Input 3/Range 2

15.

Zero/Span Input 1 Range Jumper

16.

Zero/Span Input 2 Range Jumper

17.

Zero/Span Input 3 Range Jumper

18.

Zero/Span Output 1

19.

Zero/Span Output 2

Advertising