Series 9205 Operations Manual Rev A

96

appropriate zone assignments whenever a set point is to be sent to the temperature controller. The

temperature set point is sent to every instrument number in the temperature zone assignment.

If the

ZONE_OFF

(Zone Offset) opcode had been used in the program, the set point sent to the specified

zone instrument would have the offset added. For example, a 3-zone pit furnace, where the bottom zone

usually has a higher set point. The middle zone and the top zone usually have a lower set point. The bottom

zone temperature controller is assigned to zone 1, the middle temperature controllers to zone 2, and the

top zone controller to zone 3.

If the first three steps of a program are as shown below, then the bottom zone set point is 1775, the middle

zone is 1750, and the top zone is 1800.

Step

Opcode

Temperature

Option

1

ZONE_OFF

25

Zone 1

2

ZONE_OFF

50

Zone 3

3

SETPT

1750

The first step sets the offset for zone 1 to 25 degrees; therefore, the bottom zone controller would be sent a

set point of 1775 when step 3 is executed. Likewise step 2 sets the offset for zone 3 to 50 degrees. The top

zone then receives a set point of 1800. The middle zone controller would receive the 1750. The temperature

controller displayed on the Status Display is instrument #2. If instrument #2 were the top zone controller

then the Status Display would show the 1800-degree set point.

When using the multi-zone offset feature, the temperature controller assigned as instruments 1 and 2

should be in zones that will not be offset.

Atm Instrument

This will allow the user to set the atmosphere instrument for the zone assignment. The options are

Loop 1

Instrument 5

Instrument 12

Instrument 19

Loop 2

Instrument 6

Instrument 13

Instrument 20

Loop 3

Instrument 7

Instrument 14

Instrument 21

Instrument 1

Instrument 8

Instrument 15

Instrument 22

Instrument 2

Instrument 9

Instrument 16

Instrument 23

Instrument 3

Instrument 10

Instrument 17

Instrument 24

Instrument 4

Instrument 11

Instrument 18

Instrument 25

Atm Zone Number

This option will allow the user to set the zone number for the assignment. The range is 0 – 5.

Atm Zone Offset

This option will allow the user to enter an offset for the assignment. The range is -4000 – 4000.

Temp Instrument

This will allow the user to set the temperature instrument for the zone assignment. The options are:

Loop 1

Instrument 5

Instrument 12

Instrument 19

Loop 2

Instrument 6

Instrument 13

Instrument 20

Loop 3

Instrument 7

Instrument 14

Instrument 21

Instrument 1

Instrument 8

Instrument 15

Instrument 22

Instrument 2

Instrument 9

Instrument 16

Instrument 23

Instrument 3

Instrument 10

Instrument 17

Instrument 24

Instrument 4

Instrument 11

Instrument 18

Instrument 25