SSi Configuration and Calibration

Overview

The series 9205 can be calibrated using the Instrument Configurator software supplied with the system.

Before performing this procedure on a newly installed controller, the unit needs to be powered on for at

least 30 minutes for a warm up period.

The series 9205 has three analog inputs. Each range has a zero and span calibration value. A cold junction

trim value must be calibrated for thermocouple inputs. There are two analog outputs each with a zero and

span value.

Equipment needed

A certified calibrator(s) with the ability to source and read millivolts, milliamps and thermocouples is

required. The appropriate connection leads are also required. The operator interface method requires a PC

with the Configurator software loaded. An Ethernet crossover cable is required.

Notes

Input 1 – terminals (-) 31 and (+) 32

Input 2 – terminals (-) 29 and (+) 30

Input 3 – terminals (-) 27 and (+) 28

Output 1 – terminals (-) 24 and (+) 25

Output 2 – terminals (-) 25 and (+) 26

Calibrate Aux Analog Input

If an SSi analog input board is set up, then this menu option will be visible. For information on how to

calibrate an SSi analog input board, see the Calibrate Aux Analog Input section located at the end of this

section.

User Calibration

Click on the “click” value next to the “9205 User Calibration” field to start the user calibration. The

Calibration screen will be displayed. For complete calibration of Analog Inputs start with step #1, Zero and

Span Calibration. The Cold Junction Calibration should be performed AFTER the user has calibrated all of

the inputs and, if needed, outputs.

Step 1. Zero then Span Calibration.

The second screen (Zero/Span Calibration),

and all of the subsequent screens, will

allow the user to zero and span calibrate

the inputs and outputs for the 9205

controller (cold junction calibration will be

performed as a final step).

For a zero calibration, a value of 0 mV will

need to be sourced to the input or inputs.

In the “Zero Input X/Range Y” section,

enter the zero voltage and click on the

Calibrate button. This will calibrate the

zero range. The progress of the calibration will be shown in the progress bar at the bottom of the screen.

For a span calibration, a value of 90% of the full range (or the adjusted value) will need to be sourced to the

input or inputs.