Series 9205 Operations Manual Rev A

179

Appendix C – Setup for Carbon / Dual Temperature for Quench Control

SSi’s 9205 controller is capable of controlling %Carbon and Dual Temperature loops for the purpose of

quench tank control. This guide describes how to use SSi’s Configurator to set up the 9205 controller for

%Carbon and Dual Temperature control.

Procedure

1.

Make sure that two (2) relay outputs are available. Configure the relay outputs for Alarm 1 and

Alarm 2 under Relay Assignments. See Relay Assignments.

Configuring two relay outputs for Alarm 1 and Alarm 2 relay assignments