Series 9205 Operations Manual Rev A

90

Event Run Program Setup

Event run program setup is used to start

a program that is stored in the 9205

controller (zero for buffered) or by a

defined event input.

*Program must be configured under the

menu option

Event Control

*Used to define an event input to initiate a

program start and to define which

program to start (zero starts the last

program run) from the contact closure.

The range of programs to run is 0 to 300.

*WARNING*

If a JUMP (to another program) is used in a previous program, the program that will run

would be the last program jumped to not the first program run.

If you stop a program in a GOSUB the program that will be run will be the GOSUB.

Load T/C Configuration

Configuration of any analog input device must be completed under this menu item.

Load TC Enable

This value will manually toggle between on, on + alarms, and off.

On – T/C Enabled

On + Alarms – T/C Enabled, Programmer alarm114 provided if out of band (Default wait limits)

Off – T/C not enabled

Control TC

This value allows the user to set the TC to be part of the group of Load TCs that can hold the program if it is

out of band. The values are active or not active (shown as blank).