Wiring to the Series 9205 operator interface can be done using 232 or 485 to two connectors, comm1 (232)

or comm3 (485). The terminal strip on the lower right rear corner of the operator interface is used to

connect 24VDC power. The DB-9 port A connection is used to connect the display via 232 to the Series 9205

PID controller. The controller is connected via RS485 communication to the single-loop controllers.

Electrical Installation

The Model 9205 requires 24VDC, 4 Watt, single-phase power. A 24 VDC power supply is required

and is generally included as part of the Model 9205 system. This power supply has a universal

input that can accept between 60 and 265VAC. Power should be applied in accordance with the

electrical drawings that have been supplied. Since each installation is unique to the site, the

customer is responsible for providing adequate power and making it available to the Model 9205

power supply.

SSi requirement:

MOV’s must be wired across the isolation relay coil terminals on all isolation relays that are

connected to solenoids. Further… MOVs must be connected across the HOT and NEUTRAL wires

when the solenoid is wired to them. IT IS AN ABSOLUTE MUST to have the MOVs at BOTH

LOCATIONS.