Also available in this menu option is the availability to change the status of the relay contact with relation to

alarms. As shipped, the relay contact is open with no alarm. The user can choose either normally open or

normally closed.

Alarm 1 – Alarm 3

The user can choose either normally open or normally closed.

IP Address

The IP Address menu item is a display of the

current IP Address, IP Address Mask, and the IP

Address Gateway of the 9205 controller. Please

consult your Systems Administrator before

changing this value as it can affect communications

to the 9205 controller

,

communications between

the controller and the PLC, communications

between the controller and other devices on the

network, or to data collection systems.

This page

allows the user to change the IP Address, IP

Address Mask, and IP Address Gateway of the 9205

controller. The range for each section of the three

addresses is 0 to 255.

Note – If the IP address of

the controller is changed, then the IP address will

have to be changed in the System Settings menu

option -

. Once the IP address has been

changed, the communications will eventually go

bad and stay bad until the settings have been

updated

.

NOTE: The IP address is not typically used for communications from the touch screen to the controller, but

for communications between the controller to SuperDATA modules, PLCs, etc.

Redundant TC Setup

This option allows the operator to

choose which TC to control in a

redundant TC setup. The redundant

TC setup allows for two

thermocouples to be used and

measured from. This option can be

configured so that the higher or lower

is automatically selected or in manual

mode so that the operator can choose

which TC to use.

Band

The Band lets the user set how far apart the values of the TCs in the redundant setup can be before an

alarm is activated. The alarm can be assigned under the Relay Assignment menu option. The range for

this is -4000 to 4000.