The Cascade Setpoint Limit opcode will allow the use to set the upper and lower limits for the cascade

setpoint. The temperature data is the lower limit, and the atmosphere data is the upper limit.

DELAY

N/A

N/A

Delay Time

This opcode is used when a short delay is needed. The option value is the delay time in seconds, from 1-500

seconds.

DEV_AL

Temperature Dev/Band

Atmosphere Dev/Band

Loop

The deviation alarm opcode is used to turn the temperature or vacuum deviation alarms ON or OFF.

The Temperature Dev/ Band will determine the deviation band for the temperature deviation alarm. The

Loop will determine which type of deviation alarm to use.

The Temperature Dev/Band ranges from -301 (Disable) – 30000.

The Loop options are: Off, T. Bnd (Temperature Band), A. Bnd (Atmosphere Band), A. Bnd, T. Bnd

(Atmosphere Band and Temperature Band), T. + Dev (Temperature + Deviation), T. – Dev (Temperature –

Deviation), A. Bnd, T. + Dev (Atmosphere Band and Temperature + Deviation), A. Bnd, T. – Dev (Atmosphere

Band and Temperature – Deviation), A. + Dev (Atmosphere + Deviation), A. + Dev, T. Bnd (Atmosphere +

Deviation and Temperature Band), A. + Dev, T. + Dev (Atmosphere + Deviation and Temperature +

Deviation), A. + Dev, T. – Dev (Atmosphere + Deviation and Temperature – Deviation), A. – Dev (Atmosphere

– Deviation), A. – Dev, T. Bnd (Atmosphere – Deviation and Temperature Band), A. – Dev, T. + Dev

(Atmosphere – Deviation and Temperature + Deviation), A. – Dev, T. – Dev (Atmosphere – Deviation and

Temperature – Deviation). There is also an option for Smart Temp and Smart Atm.

The band limit can be changed by the

SET_WAIT

opcode.

DOW_INQ

N/A

N/A

Day

This opcode checks the real time clock for the day of the week. This is useful for performing operations on

a weekly basis on a specific day.

The Day is the day of the week, i.e. Sunday, Monday, Tuesday, Wednesday, Thursday, Friday, or Saturday.

EVT_IN

Temperature Setpoint

Atmosphere Setpoint

Event

This opcode waits for an input event to be turned ON or OFF depending on the Event value selected.

If the Temperature Setpoint is specified, it is considered a set point and will be sent to the appropriate

controller.

The Temperature Setpoint ranges from -301 (Disable) – 30000.

The Atmosphere Setpoint ranges from -0.01 to 99.99.

The Event options are: Event 0 ON/OFF – Event 31 ON/OFF.

EVT_OUT

Temperature Setpoint N/A

Event

This opcode waits for an output event to be turned ON or OFF depending on the Event value selected.

If the Temperature Setpoint is specified, it is considered a set point and will be sent to the appropriate

controller.

The Temperature Setpoint ranges from -301 (Disable) – 30000.

The Event options are: Event 0 ON/OFF – Event 15 ON/OFF.

G_SOAK

N/A

Wait Limit

Soak Time

This is a guaranteed soak opcode. The temperature process value must be within the deviation band to

allow the soak timer to run. If the temperature process value goes out of the deviation band, then the soak

timer will stop and wait until the temperature process value comes back into the deviation band before

starting up again.