Series 9205 Operations Manual Rev A

111

Offset

This is the starting point, the Process Variable value at which you get 4 milliamps if the output is set up as

4-20mA (or 0 milliamps if output is set up as 0-20mA). Clicking on this value will display an input box from

which the user can select a new value. The range is –32768 to 32767.

Range

This is a Process Variable value between 4 and 20 milliamps (or 0 and 20 milliamps, depending on setup). .

Clicking on this value will display an input box from which the user can select a new value. The range is –

32768 to 32767.

Note - The range, although not displayed with a decimal point, contains a decimal point that is dependent

on the process variable selected. For example, if the offset is 20 mV for 4 mA, and you want 100 mV to be 20

mA, then your range should be 80. If the process variable is temperature, then the range will be 80, since

temperature PVs do not have a decimal. If the PV is % Carbon, then the range will need to include the two

decimal points for % Carbon. So, a range of 80 will be entered as 8000.

See below for more examples

.

Current Selection

Provides the option of 4-20 mA or 0-20 mA control. Clicking on this value will display an input box with a

drop-down list from which the user can select either of the two values listed above.

Offset and Range when assigned to a control loop

Inc : 0 = 4mA, 100 = 20mA

Dec : 0 = 4mA, -100 = 20mA

Example: if 4 – 20 mA = 800 mV - 1200 mV

Offset = 800 (starting point)

Range = 400

Passcode and Alarm

There are three levels of menus in the 9205

controller - Operator, Supervisor, and

Administrator

Operator Level

These are functions typically handled by a furnace

operator and do not require a passcode. When an

operator is logged in, the lock on the toolbar will be
blue - .

Supervisor Level

These are functions typically used by a supervisor

and require a level 1 passcode. When a supervisor
is logged in, the lock on the toolbar will be gold -

. To change the level 1 passcode, or the web level 1 passcode, click on the “Level 1 Code” value (range is –

32768 to 32767) or the “Web Level 1 Code” value (range is 0 to 9999) and an input box will be displayed

where the user can select a new value.

Administrator

These are functions typically used by an administrator and require a level 2 passcode. When an
administrator is logged in, the lock on the toolbar will be green - . To change the level 2 passcode or the

web level 2 passcode, click on the “Level 2 Code” value (range is –32768 to 32767) or the “Web Level 2

Code” value (range is 0 to 9999) and an input box will be displayed where the user can select a new value.