Series 9205 Operations Manual Rev A

123

Aux Setpoint Configuration

See the menu option Slave Instrument Setup for configuration prior to using Aux Setpoint Configuration.

Aux Set Point Configuration is an automatic set point retransmission with a corresponding custom offset

and delay to one or more of the first 3 configured slave instruments. The delay is in minutes and is only

active when the set point is dropped. This feature would most commonly be used to keep the alarm set

point of an overtemp tracking the furnace's main set point (with offset). The delay allows the furnace time

to cool below the level specified so that there is no overtemp alarm when the furnace is cooling.

Retrans to Slave 1 – Retrans to Slave 3

This option will determine which control loop to

use as the retransmission value.

The options are:

Off

Loop 1

Note – If the setpoint is 0, then the retransmission

is blocked

.

Setpoint Offset Sl 1 – Setpoint Offset Sl 3

Values entered will take the decimal point of the

PV into account, but each value is entered in whole

numbers:

Carbon: 1 = 0.01

Temperature: 1 = 1

This option will apply the offset when retransmitting the value from the control loop. The range is –32768 to

32767.

Setpoint Delay Sl 1 – Setpoint Delay Sl 3

This is measured in seconds. This option will set the number of seconds to delay before retransmitting the

value from the control loop. The range is –32768 to 32767.

TC Extension Correction Curves

This menu option will allow the user to set up to three TC

correction curves for the 9205 controller. Clicking on the

“click” value for a curve will display the curve edit form.

Note: If the first “Temperature” value and the first “Error”

value are both zero, then the curve will not be set

. The

user can enter up to ten “Temperature”/“Error”

combinations. The range for the “Temperature” field is –

300 to 9999. The range for the “Error” field is –30.000 to

30.000.