Wait up, Wait down – Super Systems 9205 Series User Manual

Page 133

Advertising
background image

Series 9205 Operations Manual Rev A

132

For example, assume the PV is temperature with a 1500° set point and a wait limit of 15°. Using the SETPT

opcode, if the option is wait, the recipe will not advance until the temperature PV is 1485°-1515°.

Wait Up

When using the option wait up with a set point opcode, the recipe will not advance to the next step until the

PV value reaches or exceeds the set point. The recipe will then continue to the next step.

For example, if the PV is temperature with a set point of 1500° and the wait limit is 15°, the recipe will not

advance until the PV is at or above 1485°.

Wait Down

When using the option wait down with a set point opcode, the recipe will not advance to the next step until

the PV value reaches or falls below the set point. The recipe will then continue to the next step.

Advertising
This manual is related to the following products: