Furnace setup – Super Systems 9205 Series User Manual

Page 43

Advertising
background image

Series 9205 Operations Manual Rev A

42

Atm Zone Number

This option will allow the user to set the zone number for the assignment. The range is 0 – 5.

Atm Zone Offset

This option will allow the user to enter an offset for the assignment. The range is -4000 – 4000.

Temp Source

This will allow the user to set the temperature instrument for the zone assignment. The options are:

Loop 1

Instrument 5

Instrument 12

Instrument 19

Loop 2

Instrument 6

Instrument 13

Instrument 20

Loop 3

Instrument 7

Instrument 14

Instrument 21

Instrument 1

Instrument 8

Instrument 15

Instrument 22

Instrument 2

Instrument 9

Instrument 16

Instrument 23

Instrument 3

Instrument 10

Instrument 17

Instrument 24

Instrument 4

Instrument 11

Instrument 18

Instrument 25

Temp Zone Number

This option will allow the user to set the zone number for the assignment. The range is 0 – 5.

Zone Offset, Temp

This option will allow the user to enter an offset for the assignment. The range is -4000 – 4000.

Furnace Setup

The Furnace Setup menu option is an administrative access

only option. Do not make any adjustments on the screen

without first contacting Super Systems, Inc. at (513) 772-

0060.

PVT Type

There are nine PVT choices for the 9205:

%Carbon

Cascade

Dew Point

% Carbon + Redundant TC

Millivolts

Dew Point + Redundant TC

Multiloop

Millivolts + Redundant TC

% Carbon + Dual Temp

%Carbon: Process variable will calculate for carbon potential along with a temperature loop. Loop 1 is

based off of Input 1 (terminals 31, 32 probe sensor millivolts) and Input 2 (terminals 29, 30 probe TC).

These two inputs together constitute loop 1. Loop 2 comes from Input 3 (terminals 27, 28) which is

temperature control.

Cascade: Three loops of temperature control work together in a cascade setting.

Dew Point: Control will be for dew point along with a temperature loop. Loop 1 is based off of Input 1

(terminals 31, 32 probe sensor millivolts) and Input 2 (terminals 29, 30 probe TC). These two inputs

together constitute loop 1. Loop 2 comes from Input 3 (terminals 27, 28) which is temperature control.

%Carbon + Redundant TC: This functions the same way as the %Carbon option with an additional

thermocouple for Loop 3. The two thermocouples are used to control carbon, and the operator can choose

the setting that will be used.

Advertising
This manual is related to the following products: