Super Systems 9205 Series User Manual

Page 7

Advertising
background image

Series 9205 Operations Manual Rev A

6

Wiring

It is important to connect the controller in accordance with the wiring data given in this handbook.

Take particular care not to connect AC supplies to the low voltage power supply input. Use copper

wires for 24V DC power supply to the instrument. Ensure that the wiring of installations comply

with all local wiring regulations. For example in the United Kingdom use the latest version of the

IEE wiring regulations, (BS7671). In the USA use NEC Class 1 wiring methods.

Power Isolation

The installation must include a power isolating switch or circuit breaker. This device should be in

close proximity to the controller, within easy reach of the operator and marked as the

disconnecting device for the instrument.

Earth leakage current

Due to RFI Filtering there is an earth leakage current of less than 0.5mA. This may affect the

design of an installation of multiple controllers protected by Residual Current Device, (RCD) or

Ground Fault Detector, (GFD) type circuit breakers.

Over current protection

To protect the internal PCB tracking within the controller against excess currents, the AC power

supply to the controller and power outputs must be wired through a fuse or circuit breaker

specified in the technical specification.

Voltage rating

The maximum continuous voltage applied between any of the following terminals must not

exceed 24V DC

relay or triac output to logic, DC or sensor connections;

any connection to ground.

The controller should not be wired to VAC. The 24V DC power supply voltage across the

connections and between the power supply and ground must not exceed 2.5kV. Where occasional

voltage over 2.5kV are expected or measured, the power installation to both the instrument

supply and load circuits should include a transient limiting device.

These units will typically include gas discharge tubes and metal oxide varistors that limit and

control voltage transients on the supply line due to lightning strikes or inductive load switching.

Devices are available in a range of energy ratings and should be selected to suit conditions at the

installation.

Advertising
This manual is related to the following products: