9205 analog input board jumper settings, Nalog, Nput – Super Systems 9205 Series User Manual

Page 152: Oard, Umper, Ettings

Advertising
background image

Series 9205 Operations Manual Rev A

151

9205 Analog Input Board Jumper Settings

The 9205 analog input boards are initially set up with the following configuration:

Input 1 – Temperature/Thermocouple

In order to change

these settings, the

following steps must

be taken:

1.

If necessary,

shut down

the 9205

screen

software by

clicking on

the

Shutdown

menu option

from the

Configuration

menu

2.

Shut down

power to the

screen and

any

connected instrument

3.

Remove the cover of the 9205 instrument. This is done by removing the four (4) screws in the

corner of the 9205 instrument box, and then pushing the two (2) tabs on the side of the box outward

while pulling on the chassis

4.

Remove the analog input board

5.

In order for an input to be set up as a voltage input, a jumper must be placed on the two pins of the

input

6.

To set an input for voltage, place the gray jumper over the two pins on the desired input. To set an

input for temperature, remove the gray jumper from the two pins on the desired input.

*** WARNING: A jumper must be placed over the input before voltage inputs can be

applied or the analog input board will be damaged ***

Advertising
This manual is related to the following products: