Series 9205 Operations Manual Rev A

46

Default Wait Limits

The 9205 controller uses default wait limits in conjunction with

recipe programs using the wait, wait up, or wait down feature,

or guaranteed soaks, atmospheres, etc. The wait limits are in

place to help make sure a recipe will not continue to the next

step until the process variable is within the specified range. The

wait limits are both plus and minus the value of the setpoint

specified in the recipe.

Temp Wait Limit

This is the specific wait limit for the temperature PV. The range

is: 0 to 4000.

Atm Wait Limit

This is the specific wait limit for the atmosphere PV. Range is 0-40.

The Return button will return the user to the menu screen.

Alarm Setup

The 9205 controller can be configured to use three (3)

different alarms. Each of the alarms consists of an

alarm setpoint, alarm source, alarm type, alarm

hysteresis, smart alarm, ON delay time, and a 0 SP

blocks alarm value. The alarms come from the factory

with a default configuration dependent on the

application but also can be modified prior to shipment

to your facility or in the field by a supervisor. See the

section Appendix E – Factory Default Settings for the

9205 Controller

for more information on factory

default settings for the alarms.

Setpoint

This value is the setpoint for the alarm. Clicking on

this value will display an input box from which the

user can select a new value. The range is from

–32767 to 32767.

Alarm Source

This option will indicate the source of the alarm. The options are:

PV 1 Value

PV 2 Value

PV 3 Value

Input 1 Value

Input 2 Value

Input 3 Value

Output 1 Value

Output 2 Value

Output 3 Value

Alarm Type

This value is the type of alarm used. Options are:

Process High

Process Low

Band, Normally Open