2 - 46

Sharp PLC • 2

(JW-32CUH/33CUH)

Available PLC

Communication Setting

The recommended communication parameter setting of both PLC and POD is as follows:

PLC System Memory Setting (in case of a communication port)

Set communication condition in the system memory #234/235(for PG/COMM port 1) or #236/237(for PG/

COMM port 2) to communicate with a personal computer.

Available Memory

Port

1

19200bps

Even

Baud Rate

Parity

RS-422

Data Length

7

Transmission Control

Item

Setting of PLC

1

19200bps

Even

7

2

2

Stop Bit

Error Check

Comm. Parameter of POD

4-wire system (fixed)

Sumcheck (fixed)

Command mode (fixed)

PLC

JW-32CUH
JW-33CUH

RS-232C
PG/COMM2 [Wiring Diagram 1]
RS-422
PG/COMM1 [Wiring Diagram 2]
PG/COMM2 [Wiring Diagram 2]

Communication port
on a CPU unit

Select PLC Type

JW20

COM port

Link Unit

Wiring Diagram

16 Sharp PLC

2

16

Memory

TYPE

Remarks

X9XXX (register)

0

XXXXX (relay)

1

as word device

EXXXX (self-diagnosis)

2

bXXXX (timer counter)

3

Fn

(file register)

7

*

1